TECHNICAL DATA
SHEET |
DESCRIPTION |
Composite Cavity Fire Barrier
Combined integrity and insulation
Suitable for vertical applications
|
| WEIGHT |
3.9Kg/m²nominal |
| THICKNESS |
15mm
nominal |
BS 476 PART 6
FIRE PROPAGATION TEST
WIRA Testing Centre |
Fire Propagation Index 2.56 |
BS 476 PART 7
SURFACE SPREAD OF FLAME
WIRA testing |
Certification
to "Class 1" pass |
BS
476 Class "O" BUILDING REGULATIONS
Wira Testing Centre
|
Complies
with requirements |
BS 476 PART 20/22 1987 CLAUSE 5
Assessed to the criteria of BS.476 Part 22:1987
By Helios Consultants Ltdl |
INTEGRITY: 60
minutes
INSULATION: 60 minutes |
BS
476 PART 20: 1987/PREN 1366-3:1993
PENETRATION SYSTEM
Warrington Fire Researchl |
INTEGRITY: 60
minutes
|
SOUND
REDUCTION INDEX IN ACCORDANCE WITH THE PRINCIPLES OF BS EN ISO
140/111 1995
The University of Salford |
16
dB |
FIREFLY
TITAN complies with the requirements of the
Building Regulations
1991 (2000
edition)
Approved Document B, Appendix A, table A1, item 16 |
| PACK SIZES |
LENGTH: 6
metres nominal
WIDTH: 130cms nominal
WEIGHT: 30.41 Kg nominal |
FIREFLY
TITAN to be fitted in accordance
with manufacturer guidelines |