TECHNICAL DATA SHEET
DESCRIPTION

Composite Cavity Fire Barrier
Combined integrity and insulation
Suitable for vertical & horizontal applications

WEIGHT 2.2Kg/m²nominal
THICKNESS 10mm nominal
BS 476 PART 6
FIRE PROPAGATION TEST
WIRA Testing Centre
Fire Propagation Index 2.56
BS 476 PART 7
SURFACE SPREAD OF FLAME
WIRA testing
Certification to "Class 1" pass

BS 476 Class "O" BUILDING REGULATIONS
Wira Testing Centre

Complies with requirements
BS 476 PART 20/22 1987 CLAUSE 5
Faverdale Technology Centre &
Tested & assessed at Loss Prevention Council
INTEGRITY:   60 minutes
INSULATION: 38 minutes
BS 476 PART 20/22 1987 HORIZONTAL
Tested & assessed at Loss Prevention Council
INTEGRITY:   60 minutes
INSULATION: 38 minutes
BS 476 PART 20: 1987/PREN 1366-3: 1993
PENETRATION SYSTEM
Warrington Fire Research
INTEGRITY: 60 minutes
SOUND REDUCTION INDEX IN ACCORDANCE WITH THE PRINCIPLES OF BS EN ISO 140/111 1995
The University of Salford
16 dB
FIREFLY PLUS 60 satisfies the requirements of the
Building Regulations 1991 (2000 edition)
Approved Document B, Appendix A, table A1, item 16
PACK SIZES LENGTH:     6 metres nominal
WIDTH:       130cms nominal
WEIGHT:     17.16 Kg nominal
FIREFLY PLUS 60 to be fitted in accordance
with manufacturer guidelines
 

Tel : 01706 647 422
Fax : 01706 750 256
info@tbafirefly.co.uk